(a) appliances that use non-electric energy sources; (b) air conditioners of which the condenser-side or evaporator-side, or both, do not use air for heat transfer medium.
Commission Regulation (EU) No 206/2012 of 6 March 2012 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for air conditioners and comfort fans Text with EEA relevance
Modified by
- Commission Regulation (EU) 2016/2282of 30 November 2016amending Regulations (EC) No 1275/2008, (EC) No 107/2009, (EC) No 278/2009, (EC) No 640/2009, (EC) No 641/2009, (EC) No 642/2009, (EC) No 643/2009, (EU) No 1015/2010, (EU) No 1016/2010, (EU) No 327/2011, (EU) No 206/2012, (EU) No 547/2012, (EU) No 932/2012, (EU) No 617/2013, (EU) No 666/2013, (EU) No 813/2013, (EU) No 814/2013, (EU) No 66/2014, (EU) No 548/2014, (EU) No 1253/2014, (EU) 2015/1095, (EU) 2015/1185, (EU) 2015/1188, (EU) 2015/1189 and (EU) 2016/2281 with regard to the use of tolerances in verification procedures(Text with EEA relevance), 32016R2282, December 20, 2016
1. "air conditioner" means a device capable of cooling or heating, or both, indoor air, using a vapour compression cycle driven by an electric compressor, including air conditioners that provide additional functionalities such as dehumidification, air-purification, ventilation or supplemental air-heating by means of electric resistance heating, as well as appliances that may use water (either condensate water that is formed on the evaporator side or externally added water) for evaporation on the condenser, provided that the device is also able to function without the use of additional water, using air only; 2. "double duct air conditioner" means an air conditioner in which, during cooling or heating, the condenser (or evaporator) intake air is introduced from the outdoor environment to the unit by a duct and rejected to the outdoor environment by a second duct, and which is placed wholly inside the space to be conditioned, near a wall; 3. "single duct air conditioner" means an air conditioner in which, during cooling or heating, the condenser (or evaporator) intake air is introduced from the space containing the unit and discharged outside this space; 4. "rated capacity" (P rated ) means the cooling or heating capacity of the vapour compression cycle of the unit at standard rating conditions;5. "comfort fan" means an appliance primarily designed for creating air movement around or on part of a human body for personal cooling comfort, including comfort fans that can perform additional functionalities such as lighting; 6. "fan power input" (P F ) means the electric power input of a comfort fan in Watt operating at the declared maximum fan flow rate, measured with the oscillating mechanism active (if/when applicable).
From 1 January 2013 :single duct and double duct air conditioners shall correspond to requirements as indicated in Annex I, point 2(a). From 1 January 2013 :(a) air conditioners, except single and double duct air conditioners, shall correspond to requirements as indicated in Annex I, point 2(b) and points 3(a), 3(b), 3(c); (b) single ducts and double ducts shall correspond to requirements as indicated in Annex I, points 3(a), 3(b), 3(d); (c) comfort fans shall correspond to requirements as indicated in Annex I, points 3(a), 3(b), 3(e).
From 1 January 2014 :(a) air conditioners shall correspond to ecodesign requirements as indicated in Annex I, point 2(c); (b) single duct and double duct air conditioners shall correspond to requirements as indicated in Annex I, point 2(d).
(1) " reversible air conditioner " means an air conditioner capable of both cooling and heating;(2) " standard rating conditions " means the combination of indoor (Tin ) and outdoor temperatures (Tj ) that describe the operating conditions while establishing the sound power level, rated capacity, rated air flow rate, rated energy efficiency ratio (EER ) and/or rated coefficient of performance (rated COP ), as set out in Annex II, Table 2;rated (3) " indoor temperature " (Tin ) means the dry bulb indoor air temperature [°C] (with the relative humidity indicated by the corresponding wet bulb temperature;(4) " outdoor temperature " (Tj ) means the dry bulb outdoor air temperature [°C] (with the relative humidity indicated by the corresponding wet bulb temperature);(5) " rated energy efficiency ratio " (EER ) means therated declared capacity for cooling [kW] divided by therated power input for cooling [kW] of a unit when providing cooling atstandard rating conditions ;(6) " rated coefficient of performance " (COP ) means therated declared capacity for heating [kW] divided by therated power input for heating [kW] of a unit when providing heating atstandard rating conditions ;(7) " global warming potential " (GWP ) means the measure of how much 1 kg of the refrigerant applied in the vapour compression cycle is estimated to contribute to global warming, expressed in kg CO2 equivalents over a 100-year time horizon;GWP values considered will be those set out in Annex I to Regulation (EC) No 842/2006; for fluorinated refrigerants, the GWP values shall be those published in the Third Assessment Report (TAR), adopted by the Intergovernmental Panel on Climate Change (2001 IPCC GWP values for a 100-year period);IPCC Third Assessment Climate Change 2001. A Report of the Intergovernmental Panel on Climate Change: http://www.ipcc.ch/publications_and_data/publications_and_data_reports.shtml for non-fluorinated gases, the GWP values are those published in the first IPCC assessment over a 100-year period;Climate Change, The IPCC Scientific Assessment, J.T. Houghton, G.J. Jenkins, J.J. Ephraums (ed.) Cambridge University Press, Cambridge (UK) 1990. GWP values for mixtures of refrigerants shall be based on the formula stated in Annex I to Regulation (EC) No 842/2006; for refrigerants not included in the above references, the IPCC UNEP 2010 report on Refrigeration, Air Conditioning and Heat Pumps, dated February 2011, or newer, shall be used as a reference; (8) " off mode " is a condition in which the air conditioner or comfort fan is connected to the mains power source and is not providing any function. Also considered as off mode are conditions providing only an indication of off mode condition, as well as conditions providing only functionalities intended to ensure electromagnetic compatibility pursuant to Directive 2004/108/EC of the European Parliament and of the Council ;OJ L 390, 31.12.2004, p. 24 .(9) " standby mode " means a condition where the equipment (air conditioner or comfort fan) is connected to the mains power source, depends on energy input from the mains power source to work as intended and provides only the following functions, which may persist for an indefinite time: reactivation function, or reactivation function and only an indication of enabled reactivation function, and/or information or status display;(10) " reactivation function " means a function facilitating the activation of other modes, including active mode, by remote switch including remote control, internal sensor, timer to a condition providing additional functions, including the main function;(11) " information or status display " is a continuous function providing information or indicating the status of the equipment on a display, including clocks;(12) " sound power level " means the A-weighted sound power level [dB(A)] indoors and/or outdoors measured atstandard rating conditions for cooling (or heating, if the product has no cooling function);(13) " reference design conditions " means the combination of requirements for thereference design temperature , the maximumbivalent temperature and the maximumoperation limit temperature , as set out in Annex II, Table 3;(14) " reference design temperature " means theoutdoor temperature [°C] for either cooling (Tdesignc ) or heating (Tdesignh ) as described in Annex II, Table 3, at which thepart load ratio shall be equal to 1, and which varies according the designated cooling or heatingseason ;(15) " part load ratio " (pl(Tj) ) means theoutdoor temperature minus 16 °C, divided by thereference design temperature minus 16 °C, for either cooling or heating;(16) " season " means one of the four sets of operating conditions (available for four seasons: onecooling season , threeheating seasons: average/colder/warmer ) describing perbin the combination ofoutdoor temperatures and the number of hours these temperatures occur per season for which the unit is declared fit for purpose;(17) " bin " (with indexj ) means a combination of anoutdoor temperature (Tj ) andbin hours (hj ), as set out in Annex II, Table 1;(18) " bin hours " means the hours per season (hj ) theoutdoor temperature occurs for eachbin , as set out in Annex II, Table 1;(19) " seasonal energy efficiency ratio " (SEER ) is the overall energy efficiency ratio of the unit, representative for the whole cooling season, calculated as theReference annual cooling demand divided by theannual electricity consumption for cooling ;(20) " reference annual cooling demand " (Q ) means the reference cooling demand [kWh/a] to be used as basis for calculation of SEER and calculated as the product of theC design load for cooling (Pdesignc ) and theequivalent active mode hours for cooling (H );CE (21) " equivalent active mode hours for cooling " (H ) means the assumed annual number of hours [h/a] the unit must provide theCE design load for cooling (Pdesignc ) in order to satisfy thereference annual cooling demand , as set out in Annex II, Table 4;(22) " annual electricity consumption for cooling " (Q ) means the electricity consumption [kWh/a] required to meet theCE reference annual cooling demand and is calculated as thereference annual cooling demand divided by theactive mode seasonal energy efficiency ratio (SEERon) , and the electricity consumption of the unit forthermostat off -,standby -,off - andcrankcase heater-mode during the cooling season;(23) " active mode seasonal energy efficiency ratio " (SEERon ) means the average energy efficiency ratio of the unit in active mode for the cooling function, constructed frompart load andbin-specific energy efficiency ratio 's (EERbin(Tj) ) and weighted by thebin hours thebin condition occurs;(24) " part load " means the cooling load (Pc(Tj) ) or the heating load (Ph(Tj) ) [kW] at a specific outdoor temperatureTj , calculated as thedesign load multiplied by thepart load ratio ;(25) " bin-specific energy efficiency ratio " (EERbin(Tj) ) means the energy efficiency ratio specific for everybin j withoutdoor temperature Tj in a season, derived from thepart load, declared capacity anddeclared energy efficiency ratio (EERd(Tj) ) for specifiedbins (j ) and calculated for otherbins through inter/extrapolation, when necessary corrected by thedegradation coefficient ;(26) " seasonal coefficient of performance " (SCOP ) is the overall coefficient of performance of the unit, representative for the whole designated heating season (the value of SCOP pertains to a designated heating season), calculated as thereference annual heating demand divided by theannual electricity consumption for heating ;(27) " reference annual heating demand " (Q ) means the reference heating demand [kWh/a], pertaining to a designatedH heating season , to be used as basis for calculation of SCOP and calculated as the product of thedesign load for heating (Pdesignh) and the seasonalequivalent active mode hours for heating (H );HE (28) " equivalent active mode hours for heating " (H ) means the assumed annual number of hours [h/a] the unit must provide theHE design load for heating (Pdesignh ) in order to satisfy thereference annual heating demand , as set out in Annex II, Table 4;(29) " annual electricity consumption for heating " (Q ) means the electricity consumption [kWh/a] required to meet the indicatedHE reference annual heating demand and which pertains to a designated heating season; and is calculated as thereference annual heating demand divided by theactive mode seasonal coefficient of performance (SCOPon ), and the electricity consumption of the unit forthermostat off-, standby-, off- and crankcase heater-mode during the heating season;(30) " active mode seasonal coefficient of performance " (SCOPon ) means the average coefficient of performance of the unit in active mode for the designated heating season, constructed from thepart load, electric back up heating capacity (where required) andbin-specific coefficients of performance (COPbin(Tj) and weighted by thebin hours thebin condition occurs;(31) " electric back-up heater capacity " (elbu(Tj) ) is the heating capacity [kW] of a real or assumed electric back-up heater with COP of 1 that supplements thedeclared capacity for heating (Pdh(Tj) ) in order to meet thepart load for heating (Ph(Tj) ) in casePdh(Tj) is less thanPh(Tj) , for theoutdoor temperature (Tj );(32) " bin-specific coefficient of performance " (COPbin(Tj) ) means the coefficient of performance specific for everybin j withoutdoor temperature Tj in a season, derived from thepart load ,declared capacity anddeclared coefficient of performance (COPd(Tj) ) for specifiedbins (j ) and calculated for otherbins through inter/extrapolation, when necessary corrected by thedegradation coefficient ;(33) " declared capacity " [kW] is the capacity of the vapour compression cycle of the unit for cooling (Pdc(Tj) ) or heating (Pdh(Tj) ), pertaining to anoutdoor temperature Tj andindoor temperature (Tin ), as declared by the manufacturer;(34) " service value " (SV ) [(m3 /min)/W] means for comfort fans the ratio of themaximum fan flow rate [m3 /min] and thefan power input [W];(35) " capacity control " means the ability of the unit to change its capacity by changing the volumetric flow rate. Units are to be indicated as "fixed " if the unit can not change its volumetric flow rate, "staged " if the volumetric flow rate is changed or varied in series of not more than two steps, or "variable " if the volumetric flow rate is changed or varied in series of three or more steps;(36) " function " means the indication of whether the unit is capable of indoor air cooling, indoor air heating or both;(37) " design load " means the declared cooling load (Pdesignc ) and/or declared heating load (Pdesignh ) [kW] at thereference design temperature , wherebyfor cooling mode, Pdesignc is equal to thedeclared capacity for cooling atTj equal toTdesignc ;for heating mode, Pdesignh is equal to thepart load atTj equal toTdesignh ;(38) " declared energy efficiency ratio " (EERd(Tj) ) means the energy efficiency ratio at a limited number of specifiedbins (j ) withoutdoor temperature (Tj ), as declared by the manufacturer;(39) "d eclared coefficient of performance " (COPd(Tj) ) means the coefficient of performance at a limited number of specifiedbins (j ) withoutdoor temperature (Tj ), as declared by the manufacturer;(40) " bivalent temperature " (Tbiv ) means theoutdoor temperature (Tj ) [°C] declared by the manufacturer for heating at which thedeclared capacity equals thepart load and below which thedeclared capacity must be supplemented withelectric back up heater capacity in order to meet thepart load for heating;(41) " operation limit temperature " (Tol ) means theoutdoor temperature [°C] declared by the manufacturer for heating, below which air conditioner will not be able to deliver any heating capacity. Below this temperature, thedeclared capacity is equal to zero;(42) " cycling interval capacity " [kW] is the (time-weighted) average of thedeclared capacity over the cycling test interval for cooling (Pcycc ) or heating (Pcych );(43) " cycling interval efficiency for cooling " (EERcyc ) is the average energy efficiency ratio over the cycling test interval (compressor switching on and off), calculated as the integrated cooling capacity over the interval [kWh] divided by the integrated electric power input over that same interval [kWh];(44) " cycling interval efficiency for heating " (COPcyc ) is the average coefficient of performance over the cycling test interval (compressor switching on and off), calculated as the integrated heating capacity over the interval [kWh] divided by the integrated electric power input over that same interval [kWh];(45) " degradation coefficient " is the measure of efficiency loss due to cycling (compressor switching on/off inactive mode ) established for cooling (Cdc ), heating (Cdh ) or chosen as default value 0,25;(46) " active mode " means the mode corresponding to the hours with a cooling or heating load of the building and whereby the cooling or heating function of the unit is activated. This condition may involve on/off-cycling of the unit in order to reach or maintain a required indoor air temperature;(47) " thermostat-off mode " means a mode corresponding to the hours with no cooling or heating load whereby the cooling or heating function of the unit is switched on but the unit is not operational as there is no cooling or heating load. This condition is therefore related to outdoor temperatures and not to indoor loads. Cycling on/off in active mode is not considered as thermostat off;(48) " crankcase heater operation mode " means a condition where the unit has activated a heating device to avoid the refrigerant migrating to the compressor in order to limit the refrigerant concentration in oil at compressor start;(49) " thermostat-off mode power consumption " (P ) means the power consumption of the unit [kW] while inTO thermostat-off mode;(50) " standby mode power consumption " (P ) means the power consumption of the unit [kW] while inSB standby mode;(51) " off-mode power consumption " (P ) means the power consumption of the unit [kW] while inOFF off -mode;(52) " crankcase heater mode power consumption " (P ) means the power consumption of the unit [kW] while inCK crankcase heater operation mode;(53) " thermostat-off mode operating hours " (H ) means the annual number of hours [h/a] the unit is considered to be inTO thermostat-off mode, the value of which depends on the designated season and function;(54) " standby mode operating hours " (H ) means the annual number of hours [h/a] the unit is considered to be inSB standby mode, the value of which depends on the designated season and function;(55) " off-mode operating hours " (H ) means the annual number of hours [h/a] the unit is considered to be inOFF off -mode, the value of which depends on the designated season and function;(56) " crankcase heater mode operating hours " (H ) means the annual number of hours [h/a] the unit is considered to be inCK crankcase heater operation mode , the value of which depends on the designated season and function;(57) " nominal air flow rate " means the air flow rate [m3 /h] measured at the air outlet of indoor and/or outdoor units (if applicable) of air conditioners atstandard rating conditions for cooling (or heating, if the product has no cooling function);(58) " rated power input for cooling " (P ) means the electric power input [kW] of a unit when providing cooling atEER standard rating conditions ;(59) " rated power input for heating " (P ) means the electric power input [kW] of a unit when providing heating atCOP standard rating conditions ;(60) " electricity consumption of single and double ducts " (Q respectivelySD Q ) means the electricity consumption of single or double duct air conditioners for the cooling and/or heating mode (whichever applies) [single duct in kWh/h, double duct in kWh/a];DD (61) " capacity ratio " means the ratio of the total declared cooling or heating capacity of all operating indoor units to the declared cooling or heating capacity of the outdoor unit atstandard rating conditions ;(62) " maximum fan flow rate " (F ) means the air flow rate of the comfort fan at its maximum setting [m3 /min], measured at the fan outlet with theoscillating mechanism (if applicable) turned off;(63) " oscillating mechanism " means the capability of the comfort fan to automatically vary the direction of the air flow while the fan is operating;(64) " fan sound power level " means the A-weighted sound power level of the comfort fan while providing themaximum fan flow rate , measured at the outlet side;(65) " fan active mode hours " (H ) means the number of hours [h/a] the comfort fan is assumed to provide theCE maximum fan flow rate , as described in Annex II, Table 4.
(a) From 1 January 2013 , single duct and double duct air conditioners shall correspond to requirements as indicated in Tables 1, 2 and 3 below, calculated in accordance with Annex II. Single duct and double duct air conditioners and comfort fans shall fulfil the requirements on standby and off mode as indicated in Table 2 below. The requirements on minimum energy efficiency and maximum sound power shall relate to the standard rating conditions specified in Annex II, Table 2.Table 1 Requirements for minimum energy efficiency Double duct air conditioners Single duct air conditioners EER rated COP rated EER rated COP rated If GWP of refrigerant > 150 2,40 2,36 2,40 1,80 If GWP of refrigerant ≤ 150 2,16 2,12 2,16 1,62 Table 2 Requirements for maximum power consumption in off-mode and standby mode for single duct and double duct air conditioners and comfort fans Off mode Power consumption of equipment in any off-mode condition shall not exceed 1,00 W. Standby mode The power consumption of equipment in any condition providing only a reactivation function, or providing only a reactivation function and a mere indication of enabled reactivation function, shall not exceed 1,00 W. The power consumption of equipment in any condition providing only information or status display, or providing only a combination of reactivation function and information or status display, shall not exceed 2,00 W. Availability of standby and/or off mode Equipment shall, except where this is inappropriate for the intended use, provide off mode and/or standby mode, and/or another condition which does not exceed the applicable power consumption requirements for off mode and/or standby mode when the equipment is connected to the mains power source. Table 3 Requirements for maximum sound power level Indoor sound power level in dB(A) 65 (b) From 1 January 2013 , air conditioners, except single and double duct air conditioners, shall correspond to minimum energy efficiency and maximum sound power level requirements as indicated in Tables 4 and 5 below, calculated in accordance with Annex II. The requirements on energy efficiency shall take into account the reference design conditions specified in Annex II, Table 3 using the "Average" heating season where applicable. The requirements on sound power shall relate to the standard rating conditions specified in Annex II, Table 2Table 4 Requirements for minimum energy efficiency SEER SCOP (Average heating season) If GWP of refrigerant > 150 3,60 3,40 If GWP of refrigerant ≤ 150 3,24 3,06 Table 5 Requirements for maximum sound power level Rated capacity ≤ 6 kW 6 < Rated capacity ≤12 kW Indoor sound power level in dB(A) Outdoor sound power level in dB(A) Indoor sound power level in dB(A) Outdoor sound power level in dB(A) 60 65 65 70 (c) From 1 January 2014 , air conditioners shall correspond to requirements as indicated in the table below, calculated in accordance with Annex II. The requirements on energy efficiency for air conditioners, excluding single and double duct air conditioners, shall relate to the reference design conditions specified in Annex II, Table 3 using the "Average" heating season where applicable. The requirements on energy efficiency for single and double duct air conditioners shall relate to the standard rating conditions specified in Annex II, Table 2.Table 6 Requirements for minimum energy efficiency Air conditioners, except double and single duct air conditioners Double duct air conditioners Single duct air conditioners SEER SCOP (heating season: Average) EER rated COP rated EER rated COP rated If GWP of refrigerant > 150 for < 6 kW 4,60 3,80 2,60 2,60 2,60 2,04 If GWP of refrigerant ≤ 150 for < 6 kW 4,14 3,42 2,34 2,34 2,34 1,84 If GWP of refrigerant > 150 for 6-12 kW 4,30 3,80 2,60 2,60 2,60 2,04 If GWP of refrigerant ≤ 150 for 6-12 kW 3,87 3,42 2,34 2,34 2,34 1,84 (d) From 1 January 2014 , single duct and double duct air conditioners and comfort fans shall correspond to requirements as indicated in Table 7 below, calculated in accordance with Annex II.Table 7 Requirements for maximum power consumption in off-mode and standby mode Off mode Power consumption of equipment in any off-mode condition shall not exceed 0,50 W. Standby mode The power consumption of equipment in any condition providing only a reactivation function, or providing only a reactivation function and a mere indication of enabled reactivation function, shall not exceed 0,50 W. The power consumption of equipment in any condition providing only information or status display, or providing only a combination of reactivation function and information or status display shall not exceed 1,00 W. Availability of standby and/or off mode Equipment shall, except where this is inappropriate for the intended use, provide off mode and/or standby mode, and/or another condition which does not exceed the applicable power consumption requirements for off mode and/or standby mode when the equipment is connected to the mains power source. Power management When equipment is not providing the main function, or when other energy-using product(s) are not dependent on its functions, equipment shall, unless inappropriate for the intended use, offer a power management function, or a similar function, that switches equipment after the shortest possible period of time appropriate for the intended use of the equipment, automatically into: standby mode, or off mode, or another condition which does not exceed the applicable power consumption requirements for off mode and/or standby mode when the equipment is connected to the mains power source. The power management function shall be activated before delivery.
(a) From 1 January 2013 , as regards air conditioners and comfort fans, the information set out in points below and calculated in accordance with Annex II shall be provided on:(i) the technical documentation of the product; (ii) free access websites of manufacturers of air conditioners and comfort fans;
(b) The manufacturer of air conditioners and comfort fans shall provide laboratories performing market surveillance checks, upon request, the necessary information on the setting of the unit as applied for the establishment of declared capacities, SEER/EER, SCOP/COP values andservice values and provide contact information for obtaining such information.(c) Information requirements for air conditioners, except double duct and single duct air conditioners. Table 1 Information requirements (the number of decimals in the box indicates the precision of reporting) Information to identify the model(s) to which the information relates to: For multisplit appliances, data shall be provided at capacity ratio of 1. For staged capacity units, two values divided by a slash ("/") will be declared in each box in the section "Declared capacity of the unit" and "declared EER/COP" of the unit. If default Cd = 0,25 is chosen then (results from) cycling tests are not required. Otherwise either the heating or cooling cycling test value is required. Function (indicate if present) If function includes heating: Indicate the heating season the information relates to. Indicated values should relate to one heating season at a time. Include at least the heating season "Average". cooling Y/N Average (mandatory) Y/N heating Y/N Warmer (if designated) Y/N Colder (if designated) Y/N Item symbol value unit Item symbol value unit Design load Seasonal efficiency cooling Pdesignc x,x kW cooling SEER x,x — heating/Average Pdesignh x,x kW heating/Average SCOP/A x,x — heating/Warmer Pdesignh x,x kW heating/Warmer SCOP/W x,x — heating/Colder Pdesignh x,x kW heating/Colder SCOP/C x,x — Declared capacity for cooling, at indoor temperature 27(19) °C and outdoor temperature Tj Declared energy efficiency ratio , at indoor temperature 27(19) °C and outdoor temperature Tj Tj = 35 °C Pdc x,x kW Tj = 35 °C EERd x,x — Tj = 30 °C Pdc x,x kW Tj = 30 °C EERd x,x — Tj = 25 °C Pdc x,x kW Tj = 25 °C EERd x,x — Tj = 20 °C Pdc x,x kW Tj = 20 °C EERd x,x — Declared capacity for heating/Average season, at indoor temperature 20 °C and outdoor temperature Tj Declared coefficient of performance /Average season, at indoor temperature 20 °C and outdoor temperature Tj Tj = – 7 °C Pdh x,x kW Tj = – 7 °C COPd x,x — Tj = 2 °C Pdh x,x kW Tj = 2 °C COPd x,x — Tj = 7 °C Pdh x,x kW Tj = 7 °C COPd x,x — Tj = 12 °C Pdh x,x kW Tj = 12 °C COPd x,x — Tj = bivalent temperature Pdh x,x kW Tj = bivalent temperature COPd x,x — Tj = operating limit Pdh x,x kW Tj = operating limit COPd x,x — Declared capacity for heating/Warmer season, at indoor temperature 20 °C and outdoor temperature Tj Declared coefficient of performance /Warmer season, at indoor temperature 20 °C and outdoor temperature Tj Tj = 2 °C Pdh x,x kW Tj = 2 °C COPd x,x — Tj = 7 °C Pdh x,x kW Tj = 7 °C COPd x,x — Tj = 12 °C Pdh x,x kW Tj = 12 °C COPd x,x — Tj = bivalent temperature Pdh x,x kW Tj = bivalent temperature COPd x,x — Tj = operating limit Pdh x,x kW Tj = operating limit COPd x,x — Declared capacity for heating/Colder season, at indoor temperature 20 °C and outdoor temperature Tj Declared coefficient of performance /Colder season, at indoor temperature 20 °C and outdoor temperature Tj Tj = – 7 °C Pdh x,x kW Tj = – 7 °C COPd x,x — Tj = 2 °C Pdh x,x kW Tj = 2 °C COPd x,x — Tj = 7 °C Pdh x,x kW Tj = 7 °C COPd x,x — Tj = 12 °C Pdh x,x kW Tj = 12 °C COPd x,x — Tj = bivalent temperature Pdh x,x kW Tj = bivalent temperature COPd x,x — Tj = operating limit Pdh x,x kW Tj = operating limit COPd x,x — Tj = – 15 °C Pdh x,x kW Tj = – 15 °C COPd x,x — Bivalent temperature Operating limit temperature heating/Average Tbiv x °C heating/Average Tol x °C heating/Warmer Tbiv x °C heating/Warmer Tol x °C heating/Colder Tbiv x °C heating/Colder Tol x °C Cycling interval capacity Cycling interval efficiency for cooling Pcycc x,x kW for cooling EERcyc x,x — for heating Pcych x,x kW for heating COPcyc x,x — Degradation co-efficient cooling Cdc x,x — Degradation co-efficient heating Cdh x,x — Electric power input in power modes other than "active mode" Annual electricity consumption off mode P OFF x,x kW cooling Q CE x kWh/a standby mode P SB x,x kW heating/Average Q HE x kWh/a thermostat-off mode P TO x,x kW heating/Warmer Q HE x kWh/a crankcase heater mode P CK x,x kW heating/Colder Q HE x kWh/a Capacity control (indicate one of three options) Other items fixed Y/N Sound power level (indoor/outdoor) L WA x,x/x,x dB(A) staged Y/N Global warming potential GWP x kgCO 2 eq.variable Y/N Rated air flow (indoor/outdoor) — x/x m 3 /hContact details for obtaining more information Name and address of the manufacturer or of its authorised representative. In as much as is relevant in view of the functionality, the manufacturer shall supply the information as requested in the above Table 1 in the technical documentation of the product. For units with capacity control marked "staged", two values for the highest and lowest, noted "hi/lo" divided by a slash ("/") will be declared in each box under "Declared capacity".(d) Information requirements for single duct and double duct air conditioners. Single duct air conditioners shall be named "local air conditioners" in packaging, product documentation and in any advertisement material, whether electronic or in paper. Manufacturer shall provide information as detailed in the table below. Table 2 Information requirements Information to identify the model(s) to which the information relates to [fill in as necessary] Description Symbol Value Unit Rated capacity for cooling P for coolingrated [x,x] kW Rated capacity for heating P for heatingrated [x,x] kW Rated power input for cooling P EER [x,x] kW Rated power input for heating P COP [x,x] kW Rated Energy efficiency ratio EERd [x,x] — Rated Coefficient of performance COPd [x,x] — Power consumption in thermostat-off mode P TO [x,x] W Power consumption in standby mode P SB [x,x] W Electricity consumption of single/double duct appliances (indicate for cooling and heating separately) DD: Q DD DD: [x] DD: kWh/a SD: Q SD SD: [x,x] SD: kWh/h Sound power level L WA [x] dB(A) Global warming potential GWP [x] kgCO 2 eq.Contact details for obtaining more information Name and address of the manufacturer or of its authorised representative. (e) Information requirements for comfort fans. Manufacturer shall provide information as detailed in the table below. Table 3 Information requirements Information to identify the model(s) to which the information relates to [fill in as necessary] Description Symbol Value Unit Maximum fan flow rate F [x,x] m 3 /minFan power input P [x,x] W Service value SV [x,x] (m 3 /min)/WStandby power consumption P SB [x,x] W Fan sound power level L WA [x] dB(A) Maximum air velocity c [x,x] meters/sec Measurement standard for service value [state here the reference to measurement standard used] Contact details for obtaining more information Name and address of the manufacturer or of its authorised representative.
(a) European cooling and heating season(s), as defined in Table 1 below; (b) reference design conditions, as defined in Table 3 below; (c) electric energy consumption for all relevant modes of operation, using time periods as defined in Table 4 below; (d) effects of the degradation of the energy efficiency caused by on/off cycling (if applicable) depending on the type of control of the cooling and/or heating capacity; (e) corrections on the seasonal coefficients of performance in conditions where the heating load can not be met by the heating capacity; (f) the contribution of a back-up heater (if applicable) in the calculation of the seasonal efficiency of a unit in heating mode.
COOLING SEASON | ||
---|---|---|
1 | ||
2 | ||
3 | ||
4 | ||
5 | ||
6 | ||
7 | ||
8 | ||
9 | ||
10 | ||
11 | ||
12 | ||
13 | ||
14 | ||
15 | ||
16 | ||
17 | ||
18 | ||
19 | ||
20 | ||
21 | ||
22 | ||
23 | ||
24 | ||
Total h. |
HEATING SEASON | ||||
---|---|---|---|---|
Average | Warmer | Colder | ||
1 to 8 | – 30 to – 23 | |||
9 | ||||
10 | ||||
11 | ||||
12 | ||||
13 | ||||
14 | ||||
15 | ||||
16 | ||||
17 | ||||
18 | ||||
19 | ||||
20 | ||||
21 | ||||
22 | ||||
23 | ||||
24 | ||||
25 | ||||
26 | ||||
27 | ||||
28 | ||||
29 | ||||
30 | ||||
31 | ||||
32 | ||||
33 | ||||
34 | ||||
35 | ||||
36 | ||||
37 | ||||
38 | ||||
39 | ||||
40 | ||||
41 | ||||
42 | ||||
43 | ||||
44 | ||||
45 | ||||
46 | ||||
Total h. |
Appliance | Function | ||
---|---|---|---|
air conditioners, excluding single duct air conditioners | cooling | 27 (19) | 35 (24) |
heating | 20 (max. 15) | 7(6) | |
single duct air conditioner | cooling | 35 (24) | 35 (24) |
heating | 20 (12) | 20 (12) |
Function/season | ||||
---|---|---|---|---|
Tin | Tdesignc/Tdesignh | Tbiv | Tol | |
cooling | 27 (19) | Tdesignc = 35 (24) | n.a. | n.a. |
heating/Average | 20 (15) | Tdesignh = – 10 (– 11) | max. 2 | max. – 7 |
heating/Warmer | Tdesignh = 2 (1) | max. 7 | max. 2 | |
heating/Colder | Tdesignh = – 22 (– 23) | max. – 7 | max. – 15 |
Unit | Heating season | On mode | Thermostat-off mode | Standby mode | Off mode | Crankcase heater mode | ||
---|---|---|---|---|---|---|---|---|
H | H | H | H | |||||
Cooling mode, if appliance offers cooling only | h/annum | |||||||
Cooling and heating modes, if appliance offers both modes | Cooling mode | h/annum | ||||||
Heating mode | h/annum | Average | ||||||
Warmer | ||||||||
Colder | ||||||||
Heating mode, if appliance offers heating only | h/annum | Average | ||||||
Warmer | ||||||||
Colder | ||||||||
Cooling mode, if appliance offers cooling only | h/60 min | n/a | n/a | n/a | n/a | |||
Cooling and heating modes, if appliance offers both modes | Cooling mode | h/60 min | n/a | n/a | n/a | n/a | ||
Heating mode | h/60 min | n/a | n/a | n/a | n/a | |||
Heating mode, if appliance offers heating only | h/60 min | n/a | n/a | n/a | n/a | |||
Cooling mode | h/60 min | n/a | n/a | n/a | n/a | |||
Heating mode | h/60 min | n/a | n/a | n/a | n/a |
(1) The Member State authorities shall verify one single unit of the model. (2) The model shall be considered to comply with the applicable requirements if: (a) the values given in the technical documentation pursuant to point 2 of Annex IV to Directive 2009/125/EC (declared values), and, where applicable, the values used to calculate these values, are not more favourable for the manufacturer or importer than the results of the corresponding measurements carried out pursuant to paragraph (g) thereof; and (b) the declared values meet any requirements laid down in this Regulation, and any required product information published by the manufacturer or importer does not contain values that are more favourable for the manufacturer or importer than the declared values; and (c) when the Member State authorities test the unit of the model, the determined values (the values of the relevant parameters as measured in testing and the values calculated from these measurements) comply with the respective verification tolerances as given in Table 1.
(3) If the results referred to in point 2(a) or (b) are not achieved, the model shall be considered not to comply with this Regulation. (4) If the result referred to in point 2(c) is not achieved, the Member State authorities shall select three additional units of the same model for testing. (5) The model shall be considered to comply with the applicable requirements if, for these three units, the arithmetical mean of the determined values complies with the respective verification tolerances given in Table 1. (6) If the result referred to in point 5 is not achieved, the model shall be considered not to comply with this Regulation. (7) The Member State authorities shall provide all relevant information to the authorities of the other Member States and to the Commission without delay after a decision being taken on the non-compliance of the model according to points 3 and 6.
Parameters | Verification tolerances |
---|---|
Seasonal energy efficiency ratio | The determined value shall not be lower than the declared value by more than 8 %. |
Seasonal coefficient of performance | The determined value shall not be lower than the declared value by more than 8 %. |
Power consumption in off mode | The determined value shall not exceed the declared value by more than 10 %. |
Power consumption in standby mode | The determined value shall not exceed the declared value by more than 10 %. |
Energy efficiency ratio | The determined value shall not be lower than the declared value by more than 10 %. |
Coefficient of performance | The determined value shall not be lower than the declared value by more than 10 %. |
Sound power level | The determined value shall not exceed the declared value by more than 2 dB(A). |
Air conditioners, excluding double duct and single duct air conditioners | Double duct air conditioner | Single duct air conditioner | |||
---|---|---|---|---|---|
SEER | SCOP | EER | COP | EER | COP |
Loading ...